The Orbis IS Multisensor Smoke Detector benefits from the same false alarm technology as the Optical Smoke Detector with the addition of a heat sensing element.
Key Features :
- Can be used for applications where smoke detectors are unsuitable
- Ideal for environments that are dirty or smoky under normal conditions
- Reduced incidences of false alarms
- Increased reliability of detection
Environmental Characteristics
The environmental performance is similar to that of the Orbis I.S. optical smoke detector but it should be noted that heat detectors are designed to work at particular ambient temperatures. Also classification and BASEEFA certificate number are the same as for the optical smoke detector.
Operating and storage temperature: –40°C to +70°C
Operating temperature is restricted by the intrinsic safety gas classification.
Class T5: –40°C to +45°C
Class T4: –40°C to +60°C
The detector must be protected from conditions of condensation or icing.
Specifications
Applications :
- Clean rooms
- Dusty environments
- Hazardous areas
- Offshore platforms
- Refineries
- Small to medium buildings
- Warehouses
Electrical
Maximum power-on time <20 seconds
Quiescent current: 85μA
Quiescent current tested at: 24 V DC
Sampling frequency: once every 2 seconds
Polarity L1 and L2 is sensitive to polarity
Minimum voltage of the “active detector”: 12 V
Holding voltage (min.): 5 V
Minimum voltage to light the alarm LED: 6V
Alarm reset voltage: <1 V
Alarm reset time: 1s
Alarm load: 325 Ω in series with a drop of 1.0 V
Environment
Humidity: 0% to 98% (no condensation or icing)
Nominal value: IP IP23D
Storage temperature: -40 ° C to + 70 ° C
Conformity
Approvals: BV, MED, LR, KRS, IECEx, DNV.GL, BASEEFA, BOSEC, CCS, SBSC, CPR, PESO (CCoE)
Mechanical
Weight: 80g
Colour: White
Materials: Polycarbonate housing
Product length: 50 mm
Product diameter: 100 mm
Detection principle: Photo-electric light scattering. Temperature sensitive resistance.